SORENSEN SGI200-100 DC Power Supply The Sorensen SGI200-100 represents the next generation of high power programmable DC power supplies. It is designed for exceptional load transient response, low noise and the highest power density in the industry. The power density is enhanced by a stylish front air intake allowing supplies to be stacked without any required clearance between units. The SGI combines onboard intelligent controls with the outstanding power electronics common to all SG family supplies. These controls enable sophisticated sequencing, constant power mode and save/recall of instrument settings.At the heart of the Sorensen SGI200-100 is a 5 kW power module. Four modules are configured in a single chassis to deliver 20kW of power. Combinations of these chassis can then be easily paralleled to achieve power levels up to 150 kW. Paralleled units operate like one single supply providing total system cur. Looping of sequences makes the SGI200-100 ideal for repetitive testing. An impressive vacuum fluorescent graphical display in eight languages, context sensitive “soft” keys and front panel keyboard simplify programming. Specifications of the SORENSEN SGI200-100 DC Power Supply includes: See Datasheet for Full Specifications
1D – Isolated Analog Control
E – 480VAC 3-phase (+/- 10%)
MSRP: $26,030 | In Stock!
Product Overview Sorensen SGI250-120 The Sorensen SGI250-120 is a Programmable Precision High Power DC Power Supply that is designed for exceptional load transient response, low noise and high power density which is enhanced by a stylish front air intake allowing supplies to be stacked without any required clearance between units. The SGI250-120 combines onboard intelligent controls with outstanding power electronics. These controls enable sophisticated sequencing, constant power mode and save/recall of instrument settings. Looping of sequences makes the SGI250-120 ideal for repetitive testing. An impressive vacuum fluorescent graphical display in eight languages, context sensitive “soft” keys and front panel keyboard simplify programming of the SGI250-120.Features of the Sorensen SGI250-120 include:
High Power Density: 30kW in a 6U chassis
Wide Voltage Range: 0-250Vand 0-120 Amps
Fast Load Transient Response: Protection from undesired voltage excursions
Low RMS and P-P Noise: Suitable for the most sensitive applications
Parallelable up to 150 kW: Expandable as your requirement grows
Modular Design: Upgradeable for the ultimate in investment protection
Sequencing: Program custom waveforms
Easy-to-read Fluorescent Display: Supports English, French, German, Italian, Spanish, Chinese, Japanese, and Korean languages
16-bit Resolution: Optional IEEE-488.2 + RS-232C + Ethernet provides precise control
Ethernet Control: LXI Class C compliant communication through integrated web server
Direct Relay Control: Control output and sense isolation relays, along with polarity relays. (Ethernet Option Only)
Hardware Trigger: Ethernet Option Only
Specifications of the Sorensen SGI250-120 include:Common:
Remote Sense: Load-line loss compensation for models <= 100 V is 10% above full scale voltage total (5% per load-line), and models > 100 V is 4% above full scale voltage total (2% per load-line).
Parallel Operation: Up to 5 units may be paralleled for additional cur within the power supply single-unit specifications, with exception of the DC output cur set accuracy. Additional paralleled SG units will add 0.3% inaccuracy per unit. To parallel more than 5 units,contact factory.
Series Operation: Up to 2 units (see Output Float Voltage)
Input:
Nominal Voltage 3 phase, 3 wire + ground: 208/220 VAC (operating range 187 – 242 VAC); 380/400 VAC (operating range 342 – 440 VAC); and 440/480 VAC (operating range 396 – 528 VAC)
Frequency: 47 – 63Hz (optional 400Hz @ 208VAC, does not carry CE, UL or CSA markings)
Power Factor: >0.9 typical at 208/220 VAC input; >0.78 typical at 380/400 VAC input; and >0.69 typical at 440/480 VAC input
Protection (typical): ½ cycle ride-though on all three phases, 3 cycle ride through on single phase; missing phase shutdown (800V model 6.4 msec on all 3 phases)
Environmental:
Operating Temperature: 0 to 50º C
Storage Temperature: -25º C to 65º C
Humidity Range: Relative humidity up to 95% non-condensing, 0º C – 50º C
Altitude: Operating full power available up to 5,000 ft. (~1,500 m), derate 10% of full power for every 1,000 feet higher; non-operating to 40,000 ft. (~12,000 m)
Cooling: Front and side air inlet, rear exhaust. Temperature controlled, variable speed fans. Units may be stacked without spacing.
Regulatory: Certified to UL/CSA 61010 and IEC/EN 61010-1, CE Compliant, Semi-F47 Compliant
Front Panel Dust Filter: 30 PPI (Pores Per Inch) – must ensure adequate airflow and / or derate max. temperature. 3U unit only.
Physical:
Dimensions: Width: 19.00” (48.3 cm), Depth 25.0” (63.5 cm) Height: 5-15 kW units: 3U – 5.25” rack mount (13.34 cm) 20-30 kW units: 6U – 10.5” rack mount (26.67 cm)
Weight: 3U < 80 lbs. (36 kg) 6U
Output:
Ripple & Noise (Voltage Mode, Typical): Ripple and noise specified at full load, nominal AC input. Noise measured with 6ft. cable, 1µf at load
Ripple (Cur Mode): <+/- 0.04% of full scale rms cur
DC Voltage Slew Rate: 45A / ms typical – resistive load
Line Regulation (with sense wires used): (±10% of nominal AC input, constant load); Voltage Mode: +/- 0.01% of full scale; and Cur Mode: +/- 0.05% of full scale
Load Regulation (with sense wires used): no load to full load, nominal AC input); Voltage Mode: +/- 0.02% of full scale; and Cur Mode: +/- 0.1% of full scale
Load Transient Response: Recovers within 1ms to +/-0.75% of full-scale of steadystate output for a 50% to 100% or 100% to 50% load change
Efficiency: 87% typical at nominal line and max load
Stability: ±0.05% of set point after 30 minute warm-up and over 8 hours at fixed line, load and temperature
Temperature Coefficient: 0.02%/ C of maximum output voltage rating for voltage set point 0.03%/ C of maximum output cur rating for cur set point
Output Float Voltage: Negative terminal within +/- 300 V of chassis potential. (We recommend the use of optional isolated analog Interface (IAI).) Supplies in “series” should be the same output voltage/cur.
Programming Specifications of the Sorensen SGI250-120 include:Front Panel Display:
Voltage Accuracy: +/- 0.1% of full scale
Cur Accuracy: +/- 0.4% of full scale
Resolution: 4.0 digits
Remote Analog Interface:
Voltage Accuracy: +/-0.25% of full scale for 0-5 V range, +/-0.5% of fullscale for 0-10 V range
Cur Accuracy: 0.8% of full scale
Remote Digital Interface:
Voltage Accuracy: +/- 0.1% of full scale
Cur Accuracy: +/- 0.4% of full scale
Resolution: +/-0.002% of full scale
OVP:
Accuracy: +/- 1% of full scale
Resolution: +/-0.002% of full scale
User I/O:
Disconnect & Polarity-reversal relay control (Only available with Ethernet Option)
Read-Back / Monitoring Specifications of the Sorensen SGI250-120 include:Front Panel Display:
Voltage Accuracy: +/- 0.1% of full scale
Cur Accuracy: +/- 0.4% of full scale
Resolution: 4.0 digits
Remote Analog Interface:
Accuracy: +/-1.0% of full scale (0 – 10V)
Remote Digital Interface:
Voltage Accuracy: +/- 0.1% of full scale
Cur Accuracy: +/- 0.4% of full scale
Resolution: +/-0.002% of full scale
User I/O:
Disconnect & Polarity-reversal relay control (Only available with Ethernet Option)